| Power |
| |
MD-52 AC |
MD-52 115 VAC |
MD-52 DC |
MD-52 36-55 VDC |
|
| Rated voltage: |
230 VAC
|
115 VAC
|
24 VDC
|
48 VDC
|
|
| Operating voltage: |
207-264 VAC
|
103-132 VAC
|
12-36 VDC
|
36-55 VDC
|
|
| Rated current: |
23 mA @ 230 VAC
|
46 mA @ 115 VAC
|
130 mA @ 12 VDC
|
50 mA @ >36 VDC
|
|
| Rated frequency: |
48-62 Hz
|
48-62 Hz
|
DC
|
DC
|
|
| Connection: |
Screw terminal
|
Screw terminal
|
Screw terminal
|
Screw terminal
|
|
| Connector size: |
0.2 – 2.5 mm2 24 – 12 AWG
|
0.2 – 2.5 mm2 24 – 12 AWG
|
0.2 – 2.5 mm2 24 – 12 AWG
|
0.2 – 2.5 mm2 24 – 12 AWG
|
|
| RS-232 |
|
Electrical specification:
|
RS-232 V.24 |
| Data rate: |
– 115.2 kbit/s |
| Connection: |
9-pos. D-sub female DCE and Screw terminal |
| Connector size: |
0.2 – 2.5 mm2, 24 – 12 AWG |
| Isolation between interfaces |
| Power to all other |
3000 V RMS @50 Hz and 60 s duration (MD-52 AC, MD-52 115 VAC). |
| Power to all other |
1500 V RMS @50 Hz and 60 s duration (MD-52 DC, MD-52 36-55 VDC). |
| Line to Line |
1500 V RMS @50 Hz and 60 s duration. |
| Standards |
| See Declaration of Conformity, DoC |
| Environmental |
| Temperature, operating: |
5 to 50°C |
| Mechanical |
| Dimension (W x H x D): |
55x100x128 mm |
| Weight: |
0.5 kg AC / 0,4 kg DC |
| Mounting: |
DIN rail |
| Degree of protection: |
IP 20 |
|